Appendix C

Sizing Multi-axis Shared-bus Configurations

Energy Calculations

The Kinetix 5500 servo drives have internal shunt resistors for dissipating
excessive energy. In addition, Bulletin 2097 external shunt resistors and Bulletin
2198 capacitor modules are available to increase the shared DC bus capacitance.

Use this table to calculate the total energy absorbing potential (joules) and
determine if a capacitor module or external shunt resistor is needed.

Table 91 - Energy Absorbing Potential

Refer to Motion Analyzer software, version 7.0 or later, for custom shunt sizing.

Kinetix 5500 Drive
Cat. No.

Internal Shunt

(1)

J

External Shunt
kJ

Capacitor Module

(1)

J

Capacitor Module, max

(2)

J

2198-H003-ERSx

427.09

12.51

N/A

N/A

2198-H008-ERSx

554.4

554.4

2198-H015-ERSx

549.01

12.521

676.32

676.32

2198-H025-ERSx

575.223

12.549

702.53

957.162

2198-H040-ERSx

601.434

22.647

728.74

983.373

2198-H070-ERSx

1827.01

27.218

1954.3

2208.95

(1) Value assumes the use of one servo drive and one capacitor module.
(2) Value assumes the use of one servo drive and the maximum number of capacitor modules allowed.