Before wiring input power to your Kinetix 5500 system, you must determine the
type of input power you are connecting to. The drive is designed to operate in
both grounded and ungrounded environments.

Grounded Power Configurations

The grounded (WYE) power configuration lets you ground your three-phase
power at a neutral point. This type of grounded power configuration is preferred.

Figure 35 - Grounded Power Configuration (WYE Secondary)

The Kinetix 5500 drive has factory-installed grounding screws for grounded
power distribution.

Refer to

Power Wiring Examples

beginning on

page 190

for input power

interconnect diagrams.

ATTENTION: Ungrounded and corner-grounded input power configurations are
permitted, but you must remove the ground screws.

Refer to

Removing the Grounding Screws in Ungrounded Power Configurations

on

page 71

for more information.

L3

L2

L1

1

2

L3

L2

L1

1

2

Transformer

Three-phase

Input VAC

Phase Ground

Transformer (WYE) Secondary

Bonded Cabinet

Ground

Ground Grid or

Power Distribution Ground

Connect to ground stud.

Three-phase

AC Line Filter

Input Fusing

Kinetix 5500 Servo Drive

(top view)

IMPORTANT

If you determine that you have grounded power distribution in your plant, you
do not need to remove the grounding screws.