Rockwell Automation 2198-Hxxx Kinetix 5500 Servo Drives User Manual User Manual

Page 37

Advertising
background image

Rockwell Automation Publication 2198-UM001D-EN-P - May 2014

37

Planning the Kinetix 5500 Drive System Installation

Chapter 2

These illustrations show details of recommended bonding practices for painted
panels, enclosures, and mounting brackets.

Figure 14 - Recommended Bonding Practices for Painted Panels

Stud-mounting the Subpanel

to the Enclosure Back Wall

Stud-mounting a Ground Bus

or Chassis to the Subpanel

Subpanel

Welded Stud

Scrape Paint

Flat Washer

If the mounting bracket is coated with
a non-conductive material (anodized
or painted), scrape the material around
the mounting hole.

Star Washer

Nut

Nut

Flat Washer

Mounting Bracket or

Ground Bus

Use a wire brush to remove paint from
threads to maximize ground connection.

Back Wall of
Enclosure

Welded Stud

Subpanel

Star Washer

Use plated panels or scrape paint on
front of panel.

Subpanel

Nut

Nut

Star Washer

Flat Washer

Star Washer

Star Washer

Scrape paint on both sides of
panel and use star washers.

Tapped Hole

Bolt

Flat Washer

Ground Bus or

Mounting Bracket

If the mounting bracket is coated with
a non-conductive material (anodized
or painted), scrape the material around
the mounting hole.

Bolt-mounting a Ground Bus or Chassis to the Back-panel

Advertising