Chapter 2

Planning the Kinetix 5500 Drive System Installation

External Shunt Resistor

Observe these guidelines when mounting your external shunt resistor outside of
the enclosure:

Mount shunt resistor and wiring in the very dirty zone or in an external

shielded enclosure.

Mount resistors in a shielded and ventilated enclosure outside of the

cabinet.

Keep unshielded wiring as short as possible. Keep shunt wiring as flat to

the cabinet as possible.

Figure 17 - External Shunt Resistor Outside the Enclosure

C

C

D

D

VD

D

D

C

VD

Dirty Wireway

Clean Wireway

Single Motor Cable

Very Dirty Connections Segregated

(not in wireway)

Customer-supplied

Metal Enclosure

150 mm (6.0 in.)
clearance (min) on all four
sides of the shunt resistor.

Enclosure

Metal Conduit (where
required by local code)

No sensitive

equipment within

150 mm (6.0 in.).

Shunt Power Wiring Methods:

Twisted pair in conduit (1st choice).

Shielded twisted pair (2nd choice).

Twisted pair, two twists per foot (min) (3rd choice).

Circuit

Breaker

Digital Inputs

and Ethernet Cables

Route single motor cables
in shielded cable.

Route registration and communication

signals in shielded cables.

Kinetix 5500 Servo Drive System

24V DC

Power Supply

AC Line Filter

(required for CE)

Module Status

Safety Cable

(2198-Hxxx-ERS drives only)