Kinetix 5500 Safe Torque-off - Hardwired Safety

Safe Torque-off Connector
Data

The 10-pin connector consists of two parallel 5-pin rows for cascading safety
connections from drive-to-drive in multi-axis configurations.

Figure 69 - Pin Orientation for 10-pin Safe Torque-off (STO) Connector

Table 75 - Safe Torque-off (STO) Connector Pinouts

Wire the Safe Torque-off
Circuit

This section provides guidelines for wiring your Kinetix 5500 safe torque-off
drive connections.

Pin 1

SB+

SB-

S1

SC

S2

STO Pin

Description

Signal

1

Safety bypass plus signal. Connect to both safety inputs to disable the STO function.

SB+

2

Safety bypass minus signal. Connect to safety common to disable the STO function.

SB-

3

STO input 1 (SS_IN_CH0).

S1

4

STO input common (SCOM).

SC

5

STO input 2 (SS_IN_CH1).

S2

IMPORTANT

The National Electrical Code and local electrical codes take precedence over the
values and methods provided.

IMPORTANT

To improve system performance, run wires and cables in the wireways as
established in

Establishing Noise Zones

beginning on

page 39

IMPORTANT

Pins 1 and 2 (SB+ and SB-) are used to disable the safe torque-off function.
When wiring to the STO connector, the 24V supply (for an external safety
device that triggers the safe torque-off request) must come from an
external source, otherwise system performance is jeopardized.