Standalone Drive Systems

Table 6 - Fuse Selection (Bussmann part numbers)

Table 7 - Circuit Breaker Selection (Allen-Bradley catalog numbers)

Shared DC (common-bus) Drive Systems

Table 8 - Fuse Selection (Bussmann part numbers)

Table 9 - Circuit Breaker Selection (Allen-Bradley catalog numbers)

Kinetix 5500 Drive Cat. No.

Three-phase

Single-phase

2198-H003-ERSx

KTK-R-3

KTK-R-2

2198-H008-ERSx

KTK-R-7

KTK-R-5

2198-H015-ERSx

KTK-R-15

KTK-R-10

2198-H025-ERSx

KTK-R-20

N/A

2198-H040-ERSx

KTK-R-25

2198-H070-ERSx

LPJ-35SP

Kinetix 5500 Drive Cat. No.

Three-phase

(1)

(1) UL has not approved circuit breakers for use as branch circuit protection for Kinetix 5500 drive systems.

Single-phase

(1)

2198-H003-ERSx

140U-D6D3-B20

140U-D6D2-B10

2198-H008-ERSx

140U-D6D3-B60

140U-D6D2-B20

2198-H015-ERSx

140U-D6D3-C12

140U-D6D2-B80

2198-H025-ERSx

140U-D6D3-C20

N/A

2198-H040-ERSx

140U-D6D3-C25

2198-H070-ERSx

N/A

Kinetix 5500 Drive Cat. No.

Three-phase

2198-H003-ERSx

KTK-R-10

2198-H008-ERSx

2198-H015-ERSx

KTK-R-15

2198-H025-ERSx

KTK-R-20

2198-H040-ERSx

KTK-R-25

2198-H070-ERSx

LPJ-35SP

Kinetix 5500 Drive Cat. No.

Three-phase

(1)

(1) UL has not approved circuit breakers for use as branch circuit protection for Kinetix 5500 drive systems.

2198-H003-ERSx

N/A

2198-H008-ERSx

2198-H015-ERSx

140U-D6D3-C15

2198-H025-ERSx

140U-D6D3-C20

2198-H040-ERSx

140U-D6D3-C25

2198-H070-ERSx

N/A