Ungrounded power configurations – Rockwell Automation 2198-Hxxx Kinetix 5500 Servo Drives User Manual User Manual

Page 70

Advertising
background image

70

Rockwell Automation Publication 2198-UM001D-EN-P - May 2014

Chapter 5

Connecting the Kinetix 5500 Drive System

Figure 36 - Corner Grounded (B-phase) Power Configuration (Delta Secondary)

Refer to

Power Wiring Examples

beginning on

page 190

for input power

interconnect diagrams.

Ungrounded Power Configurations

The ungrounded power configuration (

Figure 37

) does not provide a neutral

ground point.

L3

L1

L2

1

2

L3

L2

L1

1

2

Transformer (Delta) Secondary

Bonded Cabinet

Ground

Transformer

Ground Grid or

Power Distribution Ground

Connect to ground stud.

Three-phase

AC Line Filter

Input Fusing

Kinetix 5500 Servo Drive

(top view)

IMPORTANT

Even though corner-grounded power configurations have a ground
connection, treat them as ungrounded when installing Kinetix 5500 drive
systems.

IMPORTANT

If you determine that you have ungrounded or high-impedance grounded
power distribution in your facility, you need to remove the grounding screws.

Refer to

Removing the Grounding Screws in Ungrounded Power Configurations

on

page 71

for more information.

Advertising