Kinetix 5500 Safe Torque-off - Hardwired Safety

Chapter 9

Cascade the Safe Torque-off Signal

The total number of drives in a single cascaded safety circuit is limited due to the
current carrying capacity of the cascaded safety wiring. Refer to

Table 77

for

current rating per channel, per drive.

Figure 72 - Cascaded Safe Torque-off Wiring

Safe Torque-off
Specifications

To maintain safety rating, Kinetix 5500 drives must be installed inside protected
control panels or cabinets appropriate for the environmental conditions of the
industrial location. The protection class of the panel or cabinet must be IP54 or
higher.

Table 77 - Safe Torque-off Signal Specifications

Pin 1

SB+

SB-

S1

SC

S2

Pin 1

24V DC

First Drive

Middle Drive

Last Drive

Dual-channel
Equivalent
Safety Device

Attribute

Value

Safety inputs
(per channel)

Input current

< 10 mA

Input ON voltage range

18…26.4V DC

Input OFF voltage, max

5V DC

Input ON current

10 mA , each drive

(1)

(1) The maximum number of drives cascaded with safe torque-off wiring is 50.

Input OFF current

2 mA @ V in < 5V DC

Pulse rejection width

700

µs

External power supply

SELV/PELV

Input type

Optically isolated and reverse voltage protected