Troubleshooting the Kinetix 5500 Drive System

Chapter 7

NODE FLT 06 – LOST CTRL CONN

Lost Controller Connection Fault

Communication with the controller has been lost.

• Check Ethernet connection
• Check controller and Ethernet switch operation

NODE FLT 07 – CLOCK SYNC

Clock Sync Fault

Drive's local clock has lost synchronization with
controller's clock and was not able to resynchronize
within allotted time.

• Check Ethernet connection
• Check controller and Ethernet switch operation

NODE FLT 09 – DUPLICATE IP ADDRESS

Duplicate IP Address Fault

Several consecutive updates from the controller have
been lost.

Select an IP address not already in use on the network

Table 60 - NODE FLT Fault Codes (continued)

Exception Code on Display

Exception Text

Problem

Possible Solutions

Table 61 - NODE ALARM Fault Codes

Exception Code on Display

Exception Text

Problem

Possible Solutions

NODE ALARM 01 – LATE CTRL UPDATE

Control Connection Update
Alarm

Updates from the controller have been late.

• Remove unnecessary network devices from the motion network
• Change network topology so that fewer devices share common

paths

• Use high performance network equipment
• Use shielded cables
• Separate signal wiring from power wiring

NODE ALARM 03 – CLOCK JITTER

Clock Jitter Alarm

The sync variance has exceeded the sync threshold while
the device is running in sync mode.

• Check the Ethernet connection
• Check controller and Ethernet switch operation

NODE ALARM 04 – CLOCK SKEW ALARM

Clock Skew Alarm

The controller time and the drive’s time are not the same.

• Check the Ethernet connection
• Check controller and Ethernet switch operation

NODE ALARM 05 – CLOCK SYNC ALARM

Clock Sync Alarm

Drive's local clock has lost synchronization with controller's
clock for a short time during synchronous operation.

• Check the Ethernet connection
• Check controller and Ethernet switch operation