Rockwell Automation Publication 2198-UM001D-EN-P - May 2014

177

Kinetix 5500 Safe Torque-off - Integrated Safety

Chapter 10

5. Verify that the Network Status (NET) status indicator is alternating red/

green on the correct drive.

6. Click Yes to set the SNN and accept the replacement drive.

Scenario 2- Replacement Integrated Safety Drive SNN Is Different from Original and Safety
Signature Exists

1. Remove and replace the existing integrated safety drive.
2. Right-click the replacement drive and choose Properties.
3. Click the Safety tab.

4. Click Reset Ownership.
5. Click OK.
6. Right-click the replacement drive and choose Properties.