SECTION 6 - JLG CONTROL SYSTEM

3121448

– JLG Lift –

6-27

ST4A OPEN X23J -

X700AJ Only

ON

Outrigger N° 4 completely opened – the switch is released and A line is closed

OFF

Outrigger N° 4 closed or partially opened – the switch is pressed and A line is
opened

ST4B OPEN X23J -

X700AJ Only

ON

Outrigger N° 4 completely opened – the switch is released and B line is closed

OFF

Outrigger N° 4 closed or partially opened – the switch is pressed and B line is
opened

ESSICAE A

ON

The aerial part safeties are disconnected through the key button (emergency
condition) – “A” line of the aerial part safeties by-pass button is closed.

OFF

The aerial part safeties are connected (normal working condition) – “A” line of the
aerial part safeties by-pass button is opened

ESSICAE B

ON

The aerial part safeties are disconnected through the key button (emergency
condition) – “B” line of the aerial part safeties by-pass button is closed.

OFF

The aerial part safeties are connected (normal working condition) – “B” line of the
aerial part safeties by-pass button is opened

ESSICC A

ON

The ground part safeties are disconnected through the key button (emergency
condition)– “A” line of the ground part safeties by-pass button is closed.

OFF

The ground part safeties are connected (normal working condition) – “A” line of the
ground part safeties by-pass button is opened

ESSICC B

ON

The ground part safeties are disconnected through the key button (emergency
condition)– “B” line of the ground part safeties by-pass button is closed.

OFF

The ground part safeties are connected (normal working condition) – “B” line of the
ground part safeties by-pass button is opened

EM GND A

ON

Emergency stop on the ground is released –“A” line of the emergency stop is
closed

OFF

Emergency stop on the ground is pressed – “A” line of the emergency stop is
opened

EM GND B

ON

Emergency stop on the ground is released –“B” line of the emergency stop is
closed

OFF

Emergency stop on the ground is pressed – “B” line of the emergency stop is
opened

FOTO A

ON

Photocell A receives the signal from the reflector (Aerial part closed and aligned)

OFF

Photocell A does not receive the signal from the reflector (Aerial part opened)

FOTO B

ON

Photocell B receives the signal from the reflector (Aerial part closed and aligned)

OFF

Photocell B does not receive the signal from the reflector (Aerial part opened)

FREE

ON

Do not consider this signal

EM.R.C.GND

ON

The emergency stop on ground remote control is released.

OFF

The emergency stop on ground remote control is pressed or the ground remote
control is disconnected