SECTION 6 - JLG CONTROL SYSTEM

6-40

– JLG Lift –

3121448

Table 6-6. INVERTER Diagnostic trouble code chart

CODE

MEANING

1

Wrong Config

Cause: Eeprom memory not configured

Solution: Contact JLG after sales dept.

8

Watch Dog

Cause: The inverter is unable to activate or turn off the electric motor

Solution: Control connections and continuity of the electric motor. If they are OK replace
the inverter

13

Eeprom KO

Cause: Hardware or Software problem in eeprom

Solution: Replace the inverter

16

Aux output KO

Cause: Electromechanical brake problem

Solution: Usually it is a temporary anomaly due to a particular working condition. In case
the anomaly persists replace the inverter.

17

Logic failure #3

Cause: Activates in case of high peak of current in the inverter.

Solution: Usually it is a temporary anomaly due to a particular working condition. In case
the anomaly persists replace the inverter.

18

Logic Failure #2

Cause: Fault in the inverter

Solution: Replace the inverter

19

Logic failure #1

Cause:

An overvoltage or a sudden voltage drop occurred.

Solution: Usually it is a temporary anomaly due to a particular working condition. In
case the anomaly persists replace the inverter.

30

VMN low

Cause: Inverter supply voltage is lower than the batteries’ one, or the connection
with the positive terminal of the battery is not correct.

Solution: Control the connection with the positive terminal of the battery. If the anomaly
persists replace the inverter.

31

VMN High

Cause: One motor phase is not correctly connected or is broken.

Solution: Control motor phases. If the anomaly persists replace the inverter.

37

Contactor closed

Cause: The relay remains closed with power to the coil disconnected.

Solution: Control the relay