Device control – Lenze 931M-931W User Manual

Page 101

Advertising
background image

Device control

State diagram

Control word

8

101

KHB 13.0003-EN

2.0

Bits 0 ... 3 are used for status transitions. The required commands are listed in the below

table. The

Fault reset

command is activated by a LOW-HIGH transition of bit 7.

Command

Bit 15

Bit 7

Bit 3

Bit 2

Bit 1

Bit 0

Shutdown

1

X

X

1

1

0

Switch on

1

X

X

1

1

1

Disable voltage

1

X

X

X

0

X

Quick stop

1

X

X

0

1

X

Disable operation

1

X

0

1

1

1

Enable operation

1

X

1

1

1

1

Fault reset

1

0 -> 1

X

X

X

X

Tab. 13

Overview of all commands

X not relevant

Note!

Since some status changes take a certain time, all status changes activated via

the control word must be read in the status word.
Another command may only be written via the control word when the new

status can be read in the status word.