4 electrical installation, 1 can bus wiring, Electrical installation – Lenze 931M-931W User Manual

Page 13: 4electrical installation, Stop, Can bus wiring

Advertising
background image

Electrical installation

CAN bus wiring

4

13

KHB 13.0003-EN

2.0

4

Electrical installation

4.1

CAN bus wiring

CAN_L

CAN_L

CAN_L

CAN_L

CAN_GND

CAN_GND

CAN_GND

CAN_GND

CAN_SHLD

CAN_SHLD

CAN_SHLD

CAN_SHLD

CAN_H

CAN_H

CAN_H

CAN_H

X4.1

X4.2

A

2

A

1

A

n

CAN-GND

CAN_SHLD

CAN_L

CAN_H

120

1 2

3

4 5

6

7 8

9

120

W

120

W

931m_050

Fig. 1

Basic wiring of CANopen with Sub-D connector to the master

A

1

Node 1 - master (e.g. PLC)

A

2

Node 2 - slave (e.g. 931M/W controller)

A

n

Node n - slave, n = max. 128

Stop!

Connect a 120 Ω terminating resistor to the first and last bus device.

If the last bus device is a 931M/W controller, use the »fluxx« software to activate the

terminating resistor.

Specification of the transmission cable
Please observe our recommendations for signal cables.

Bus cable specification
Cable resistance

135 - 165 Ω/km, (f = 3 - 20 MHz)

Capacitance per unit length

30 nF/km

Loop resistance

< 110 Ω/km

Wire diameter

> 0.64 mm

Wire cross-section

> 0.34 mm

2

Wires

double twisted, insulated and shielded

Advertising