Appendix, Index table – Lenze 931M-931W User Manual

Page 142

Advertising
background image

Appendix

Index table

10

142

KHB 13.0003-EN 2.0

Characteristics

Possible settings

Name

Index

Description

Selection

Lenze

6040

h

0 control word

0000

h

0000

h

{1

h

}

FFFF

h VAR

UINT1

6

RW

MAP

Changing the controller

status.

Activating an action (e.g.

homing).

Bit No.

Meaning

0

Switch on

Controlling the status

transitions. (These bits are

evaluated together).

1

Enable voltage

2

Quick stop

3

Enable operation

4 ... 6

Operation-mode specific

The bit function depends

on the operating mode.

7

Reset fault

With a zero/one

transition, the controller

tries to acknowledge the

existing errors. This is only

successful, when the cause

of the error has been

removed.

8

Stop

The bit function depends

on the operating mode.

9 ... 10

Reserve

Reserved, set to 0.

11 ... 13 Operation-mode specific

The bit function depends

on the operating mode.

14

Wait for sync

The bit function depends

on the operating mode.

15

Remote request

When this bit is set,

remote control of the

controller via the CAN bus

is requested. When this bit

is not set, local controller

operation (e.g. via the

»fluxx« software) is

enabled.

Advertising