Commissioning

Speed control

Parameterising of a process data object (TPDO and RPDO)

6

62

KHB 13.0003-EN 2.0

No. Description

Identifier Control

field

Command

code

Index

Subindex Data 1 Data 2 Data 3 Data 4

Data

length

Low

byte

High

byte

1

Network management (NMT)

For parameterising the PDO, the

network management is set to

Pre-operational (80

h

).

00

2

80

00

00

00

00

00

00

00

2

Deactivating the RPDO

The RPDO is deactivated by

setting bit 31.

601

8

23

00

14

01

01

02

00

80

3

Deleting the number of objects

For changing the object

mapping, the number of objects

(number_of_mapped_objects)

must be set to zero.

601

5

2F

00

16

00

00

00

00

00

4

Parameterising the first object

to be mapped

Here, the index of the object to

be mapped (first_mapped_

object) and the length of the

corresponding variable type

must be indicated. The first

object to be mapped is the

setpoint speed (index 60FF_00

h

)

with a length of 32 bits (20

h

).

601

8

23

00

16

01

20

00

FF

60

5

Defining the number of objects

In this example, one mapped

object (setpoint speed) is to be

transmitted (number_of_

mapped_objects).

601

5

2F

00

16

00

01

00

00

00

6

Parameterising the transmission

mode

The PDO transmission is

event-controlled and depends

on the transmission cycle time

(entry FF

h

in the transmission_

type).

601

5

2F

00

14

02

FF

00

00

00

7

Activating the RPDO

The PDO is activated by

resetting bit 31.

601

8

23

00

14

01

01

02

00

00

8

Network management (NMT)

For parameterising the PDO, the

network management is set to

Operational (01

h

).

00

2

01

00

00

00

00

00

00

00

Tab. 3

Example parameterisation of a receive PDO