Device control

State diagram

States of the drive controller

8

98

KHB 13.0003-EN 2.0

Example: Switching on the power stage (controller must be parameterised)
1. The controller is in the Switch_On_Disabled status.
2. The controller is to change to Operation_Enable.
3. Transitions 2, 3 and 4 must be executed.
4. For requesting the parameterisation authority via the CAN bus, bit 15

remote_request must be set to 1. If this is not the case, another interface (e.g. serial

interface) has got the parameterisation authority and the status machine cannot be

”enabled” or influenced via the CAN bus.

5. Ensure that no other bits are set in the control word, because only bits 0 ... 3 are

important for the transitions.

Transition Old status

Control word

New status

15 3

2

1

0

Value

2

Switch_On_Disabled 1

X

1

1

0

8006

h

Ready_To_Switch_On

1)

3

Ready_To_Switch_

On

1

X

1

1

1

8007

h

Switched_On

1)

4

Switched_On

1

1

1

1

1

800F

h

Operation_Enable

1)

1)

The master must wait until the status can be read in the status word.

Transitions 3 and 4 can be combined by setting the control word directly to 000F

h

. The set

bit 3 is not relevant for status transition 2.

8.1.3

States of the drive controller

Status

Meaning

Not_Ready_To_Switch_On

The controller makes a self-test. CAN communication is not active yet.

Switch_On_Disabled

The self-test has been completed. CAN communication is possible.

Ready_To_Switch_On

The controller is waiting for the switch-on command, depending on the

controller enable logic.

Switched_On

1

)

The power stage is switched on.

Operation_Enable

1

)

Voltage is applied and the motor is controlled according to the operating

mode.

Quick_Stop_Active

1

)

The quick stop function is carried out (see: quick_stop_option_code). Voltage

is applied and the motor is controlled according to the quick stop function.

Fault_Reaction_Active

1)

An error has occurred. With critical errors, the status changes to Fault

immediately. Otherwise, the action selected in the

fault_reaction_option_code is activated. Voltage is applied and the motor is

controlled according to the Fault Reaction function.

Fault

An error has occurred. The motor is deenergised.

Tab. 11

Controller states

1)

The power stage is switched on