CANopen communication

Heartbeat telegram

Description of the objects

5

55

KHB 13.0003-EN

2.0

5.7.2

Description of the objects

Index

Name

Possible settings

Characteristics

Lenze

Selection

Description

1016

h

Consumer_

heartbeat_time

0 number_of_entries

01

h

{1

h

}

7F

h VAR

UINT8

RO

Maximally supported

subindices.

01

h

1 subindex is supported.

1 consumer_

heartbeat_time

0

{1 ms}

65535

VAR

UINT32 RW

Setting the time in which the

controller expects a message

from the master. The time

must be longer than the

corresponding index

producer_heartbeat_time.

”0” means that the function

is deactivated.

Bit No.
0 - 15

Heartbeat time

16 - 23

Node address of the

controller.

24 - 31

Reserved, value 0.

1017

h

0 producer_

heartbeat_time

0

0

{1 ms}

65536

VAR

UINT16 RW

Time between two heartbeat

telegrams.

If the controller starts with a

time unequal zero, the

boot-up telegram is the first

heartbeat.

0

Function is deactivated.