Appendix

Index table

10

121

KHB 13.0003-EN

2.0

Characteristics

Possible settings

Name

Index

Description

Selection

Lenze

1006

h

0 communication_

cycle_period

0

{1 μs}

VAR

UINT3

2

RO

Setting the cycle time of

synchronisation messages.

0

No synchronisation

message sending.

1007

h

0 synchronous_

window_length

0

{1 μs}

VAR

UINT3

2

RO

Setting the time slot in

which the sync telegrams

are sent.

0

Function is deactivated.

1008

h

0 manufacturer_

device_name

VAR

STR

RO

Manufacturer’s controller

name.

1009

h

0 manufacturer_

hardware_version

VAR

STR

RO

Current hardware version.

100A

h

0 manufacturer_

software_version

VAR

STR

RO

Current software version.

100C

h

0 guard_time

0

0

{1 ms}

65535

VAR

UINT1

6

RW

Setting the cyclic

monitoring time in which

the master queries the

status of the slaves.

0

Function is deactivated.

100D

h

0 life_time_factor

0

0

{1}

255

VAR

UINT8

RW

The maximum time

between two queries of

the master results from

the product of guard_time

and life_time_

factor.

0

Function is deactivated.

1010

h

Store_parameters

0 largest_supported_

subindex

VAR

UINT8

RO

1 save_all_

parameters

00000001

h

00000000

h

{1

h

}

65766173

h —

UINT3

2

RW

Accepting the default

parameter set in the

application parameter set.

00000000

h

Default parameter set is

not accepted.

65766173

h

Save

Default parameter set is

accepted.