3 position control, 1 parameterising of the homing run, Parameterising of the homing run – Lenze 931M-931W User Manual

Page 66: Commissioning

Advertising
background image

Commissioning

Position control

Parameterising of the homing run

6

66

KHB 13.0003-EN 2.0

6.3

Position control

The following example describes the parameterisation and execution of homing. A

controller with node address 1 is used as communication device. In addition, the

commissioning of a position control will be explained.
Select the settings for the lower-level speed control as described in chapter 6.2.2. The

following explanation is based on these controller settings.

6.3.1

Parameterising of the homing run

Before homing is started, the homing method, homing speed and accelerations have to be

defined. After this, the home position can be approached.

No. Description

Identifier Control

field

Command

code

Index

Subindex Data 1 Data 2 Data 3 Data 4

Data

length

Low

byte

High

byte

1

Selecting the operating mode

Homing

Homing (06) is used as

operating mode (modes_of_

operation).

601

5

2F

60

60

00

06

00

00

00

2

Defining the homing method

Traversing to the negative limit

switch under consideration of

the zero pulse (value 1) is

selected as homing method.

Alternative setting: current

position (value 35).

601

5

2F

98

60

00

01

00

00

00

3

High homing speed setting

The search speed used while

searching for the limit switch

(speed_during_search_for_swit

ch) is set to 100 rpm.

601

6

2B

99

60

01

64

00

00

00

4

Low homing speed setting

The search speed used while

searching for the zero pulse

(speed_during_search_for_zero)

is set to 50 rpm.

601

6

2B

99

60

02

32

00

00

00

Tab. 6

Parameterisation of homing

The homing status can be seen from the status word. Bit 12 indicates whether homing has

been completed (homing_attained) or is still being carried out.
Unlike the other operating modes, this operating mode requires another step after the

status change to operation enabled when traversing the status machine. Then, homing is

started through bit 4 of the control word.