Commissioning

Activation of CANopen

6

59

KHB 13.0003-EN 2.0

6

Commissioning

6.1

Activation of CANopen

The controllers are default set to CAN bus communication.

931m_100

In the CAN Bus field, three parameters must be set:

ƒ

Node ID

For an unambiguous identification in the network, a node address must be assigned to

each node. Each node address may onlybe assigned once inthe network.The nodeaddress

is used to address the device.

ƒ

Baud rate

This parameter determines the baud rate in kBaud or kbits/s that is used on the CAN bus.

Please observe that high baud rates require a low maximum cable length.

ƒ

Bus terminator

If the controller is the lastnode ina bus system, theterminating resistormust beactivated.
When the physical connection to the master has been established, programming can be

started.

Note!

The controllers can either be parameterised and controlled via the serial

interface using the »fluxx« software or via the CAN bus.
In case of a CAN bus parameterisation and operation, the »fluxx« software

may be maximally operated in the operating mode ”Online Level 1”. If a higher

operating mode is selected, the »fluxx« software will have the parameter

change rights. In this case, the operating status cannot be changed via the

CAN.