Canopen communication, Receive pdo – Lenze 931M-931W User Manual

Page 34

Advertising
background image

CANopen communication

Process data transfer (PDO transfer)

Objects for PDO parameterisation

5

34

KHB 13.0003-EN 2.0

2. Receive PDO

Index

Name

Possible settings

Characteristics

Lenze

Selection

Description

1401

h

Receive PDO2

communication

parameters

0 number_of_entries

00

h

{1

h

}

02

h REC

UINT8

RO

Maximally supported

subindices.

02

h

Three subindices are

supported.

1 COB-ID_used_by_

PDO

80000301

h

80000301

h

{1

h

}

800003FF

h —

UINT32 RW

Identifier of receive PDO2

(300

h

+ node address)

For processing, bit 31 must

be set (parameterisation of

mapping).

Bit No.

Value

0 - 10

X

11-bit identifier

11 - 28

0

The extended identifier

(bit 29) is not supported.

Every bit in this range must

be set to ”0”.

29

0

30

0

Set to zero.

31

0

PDO active

1

PDO inactive

2 transmission_type FF

h

0

{1}

F0

h

, FE

h

, FF

h —

UINT8

RW

Setting the transmission

mode.

0

Function is deactivated.

n = 1 ... F0

When a value n is entered,

the PDO is accepted every

n-th sync.

n = FE

Cyclic transmission mode.

n = FF

Event-controlled

transmission mode.