Rockwell Automation Publication D2-3518-3 - May 2013

103

Chapter 9

Present value of the PI error signal.

Present value of the PI output signal.

The Accel Time parameters set the rate at which the drive ramps to its output
frequency after a start command or during an increase in command frequency
(speed change). The rate established is the result of the following equation:

(Maximum Speed ÷ Accel Time) = Accel Rate

Two accel times exist to enable acceleration rate changes on the fly using a
building automation system command or digital input, if configured.

137

PI Error Meter

Range:

-/+100.00% [0.01%]

Default:

Read Only

Access:

1

Path: Speed Command > Process PI

See also:

124...138

138

PI Output Meter

Range:

100.0 Hz [0.1 Hz]

Default:

Read Only

Access:

1

Path: Speed Command > Process PI

See also:

124...138

140
141

Accel Time 1
Accel Time 2

Range:

0.1...100.0 [0.1 sec]

Default:

10.0

Access:

140 = 0
141 = 0

Path: Dynamic Control > Ramp Rates

See also:

142, 143, 146, 361...366