Troubleshooting the Drive

The LiquiFlo 2.0 AC drive provides the following ways to determine the status of
the drive and to troubleshoot problems that may occur:

LEDs on the front of the drive

User-configurable and non-configurable alarms

User-configurable and non-configurable faults

Entries in the fault queue

Drive status parameters

Verify that the DC Bus
Capacitors are Discharged
Before Servicing the Drive

The DC bus capacitors of the drive retain hazardous voltages after input power
has been disconnected. Perform the following steps before touching any internal
components.

1.

Turn off the circuit breaker and lock out input power. Wait 5 minutes.

2.

Open the enclosure door to the power module.

3.

Verify that there is no voltage at the power module’s input power terminals
(L1, L2, and L3) as shown in

Figure 2 on page 15

for Frame 3, and

Figure 5

on page 20

for Frame 4.

4.

Remove the cover of the power module.

ATTENTION: Only qualified electrical personnel familiar with the construction
and operation of this equipment and the hazards involved should install, adjust,
operate, or service this equipment. Read and understand this manual and other
applicable manuals in their entirety before proceeding. Failure to observe this
precaution could result in severe bodily injury or loss of life.

ATTENTION: DC bus capacitors retain hazardous voltages after input power has
been disconnected. After disconnecting input power, wait 5 minutes for the DC
bus capacitors to discharge and then check the voltage with a voltmeter to
ensure the DC bus capacitors are discharged before touching any internal
components. Failure to observe this precaution could result in severe bodily
injury or loss of life.