Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual

Page 83

Advertising
background image

Rockwell Automation Publication D2-3518-3 - May 2013

83

Chapter 9

Sets the maximum allowable frequency the drive will output. Note that this is not
maximum speed, which is set in parameter 82. See

Figure 36

.

See description of rectifier Max Motor Freq parameter (108 in rectifiers
parameters).

Figure 36 - Speed Limits

Enables/disables the compensation correction options.

Figure 37 - Compensation (56)

55

Maximum Freq

Range:

5.0...250.0 Hz [0.1 Hz]

Default:

130.0 Hz

Access:

0

Path: Motor Control > Torq Attributes

See also:

82, 83, rectifier 108

56

Compensation

Range:

See

Figure 37

Default:

See

Figure 37

Access:

1

Path: Motor Control > Torq Attributes

See also:

Allowable Output Frequency Range

Bus Regulation or Current Limit

V

o

l

t

a

g

e

Frequency

Allowable Output Frequency Range

Normal Operation

Allowable Reference Frequency Range

Frequency Trim due to
Speed Control Mode

Max Volts

Motor Volts

Break Volts

Start Boost

Run

0

Min

Speed

Motor

Hz

Max

Speed

Output

Freq Limit

Max
Freq

Break

Frequency

Overspeed

Limit

1

0

0

0

x

x

x

x

x

x

x

x

x

x

x

x

0

0

1

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Enabled
0 =Disabled
x =Reserved

Bit #

Factory Default Bit Values

Reflect W

av

e

Enab

le Jer

k

Ixo A

utoCalc

Extended Range

Nibble 1

Nibble 2

Nibble 3

Nibble 4