Rockwell Automation Publication D2-3518-3 - May 2013

173

Chapter 9

If Vdc Optimize (102) is set to Disabled, Vdc Reference (103) is the minimum
DC bus voltage generated by the rectifier while the rectifier or the entire drive is
running.

If Vdc Optimize (102) is set to Enabled, then Vdc Reference (103) is not used.

Displays the commanded DC bus voltage.

See Vdc Optimize (102) for more information on how the rectifier derives this
command when it or the entire drive is running.

When the rectifier is not running, this parameter matches the DC bus voltage as
measured by the rectifier, visible in DC Bus Voltage (10).

The maximum RMS current the rectifier produces expressed as

x.x A.

Sets the 100% current level for the rectifier I2T diagnostic Overload fault
(fault 220).

103

Vdc Reference

Range:

400.0...800.0V DC [x.xV DC]

Default:

700.0

Access:

0

Dynamic Control > Bus Voltage

See also:

102, 104

104

Vdc Command

Range:

400.0...800.0V DC [x.xV DC]

Default:

Read Only

Access:

0

Dynamic Control > Bus Voltage

See also:

102, 103

105

Current Limit

Range:

Rectifier Rated Amps/4 to 150% of Rectifier Rated Amps [x.x A]

Default:

110% of Rectifier Rated Amps

Access:

0

Path: Dynamic Control > Load Limits

See also:

106

Input Load Amps

Range:

0.0 A to 1000.0 A (Frame 3) or 1600.0 A (Frame 4) [0.1 A]

Default:

Rectifier Rated Amps

Access:

0

Path: Dynamic Control > Load Limits

See also:

21