Chapter 9

Figure 65 - Anlg in Sqr Root (321)

The drive scales the value read from the user-configurable analog input and
converts it to units usable for the application. You control the scaling by setting
parameters that associate a low and high point in the input range with a low and
high point in the target range.

Analog In 1 Hi sets the highest input value to the user-configurable analog input
1 scaling block. See

AC Line I/O Board Description (Frame 3 Only) on page 25

through

Combined I/O Board Description (Frame 4 Only) on page 29

for a

description of I/O hardware that is present on this drive and is controlled by the
inverter.

322

Analog In 1 Hi

Range:

4.000...20.000 mA [0.001 mA]
-/+10.000V [0.1V]
0.0...10.000V [0.1V]

Default:

20.000 mA

Access:

0

Path: Inputs & Outputs > Analog Inputs

See also:

91, 92, 320

Analog Input Scaling Example

Assume:

Speed Ref A Sel = Analog In 1

Minimum Freq = 0 Hz

Maximum Freq = 60 Hz

Analog In 1 Lo = 0.0V

Analog In 1 Hi = 10.0V

This is the default setting, where minimum input (0V) represents Minimum
Speed and maximum input (10V) represents Maximum Speed.

x

x

x

x

x

x

x

x

x

x

x

x

x

x

0

0

0

0

1

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Enable
0 =Disable
x =Reserved

Bit #

Factory Default Bit Values

Analog ln 1

Analog ln 2

Nibble 1

Nibble 2

Nibble 3

Nibble 4

Advertising