Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual

Page 153

Advertising
background image

Rockwell Automation Publication D2-3518-3 - May 2013

153

Chapter 9

Table 9 - Speed Select Inputs

Assigns an input function to the user-configurable digital inputs of the drive.
Note that digital inputs Run, Jog, Clear-Faults, and Direction control functions
are operational only when the mask parameters are set for these functions.

See

AC Line I/O Board Description (Frame 3 Only) on page 25

through

Combined I/O Board Description (Frame 4 Only) on page 29

for a description

of I/O hardware that is present on this drive and is controlled by the inverter.

Table 10 - Default Values for Parameters 361...366

The input functions are:

1 = Enable

: If the input is closed, the drive can run (start permissive). If the input

is open, the drive will not start.

If the drive is already running when this input is opened, the drive coasts and
indicates not enabled on the OIM (if present). This is not considered a fault
condition, and no fault is generated.

If multiple enable inputs are configured, the drive will not run if any of them are
open.

2 = Clear Faults:

This function allows an external device to reset drive faults

through the terminal block if clearing faults from the terminal block is enabled
using the Logic Mask (276) and Fault Clr Mask (283). An open-to-closed
transition on this input resets the current fault (if any).

Speed Select Inputs

3

2

1

Reference Source

0

0

0

Speed Ref A Sel

0

0

1

Speed Ref B Sel

0

1

0

Preset Speed 2

0

1

1

Preset Speed 3

1

0

0

Preset Speed 4

1

0

1

Preset Speed 5

1

1

0

Preset Speed 6

1 1

1

Preset

Speed

7

Parameter No.

Default Value

361

0 = Unused

362

0 = Unused

363

0 = Unused

364

0 = Unused

365

0 = Unused

366

0 = Unused