Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual

Page 48

Advertising
background image

48

Rockwell Automation Publication D2-3518-3 - May 2013

Chapter 4

Use the following procedure to lift and mount the LiquiFlo 2.0 power module:

1.

Use an overhead or portable hoist (minimum 2 ton rated capacity) to
attach a free-fall chain to the chain secured to the power module. Take up
any vertical slack in the chain.

2.

Use the hoist to carefully lift the power module from the horizontal
shipping pallet.

3.

Position the power module in the prepared mounting location.

4.

Machine fasten the power module enclosure using 1/2-inch bolts, grade 5
or better, with compression washers. Recommended tightening torque is
11.3...13.5 N•m (100...120 lb•in).

ATTENTION: Do not use input and output busbars for lifting or handling.
Otherwise, damage to equipment may result.

ATTENTION: Mechanically support conductors to minimize mechanical load on
input and output busbars. Otherwise, damage to equipment may result.

Advertising