Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual

Page 200

Advertising
background image

200

Rockwell Automation Publication D2-3518-3 - May 2013

Chapter 10

Dig In
ConflictB

2 User-configurable digital input functions are in conflict. Combinations marked with a will cause an alarm.

Dig In
ConflictC

2 More than one physical input has been configured to the same input function. Multiple configurations are not

allowed for the following input functions:

Drive OL
Level 1

1 The calculated inverter IGBT temperature requires a reduction in PWM carrier frequency. If inverter Drive OL Mode

(150) is disabled and the load is not reduced, an overload fault eventually occurs.

Drive OL
Level 2

1 The calculated inverter IGBT temperature requires a reduction in Current Limit. If inverter Drive OL Mode (150) is

disabled and the load is not reduced, an overload fault eventually occurs.

Flux Amps Ref
Rang

2 Result of autotune procedure (inverter 61).

IntDBRes
OvrHeat

1 The drive has temporarily disabled the dynamic braking regulator because the resistor temperature has exceeded

a predetermined value.

IR Volts Range

2 The drive autotuning default is Calculate and the value calculated for IR Drop Volts is not in the range of

acceptable values. This alarm should clear when all motor nameplate data is properly entered.

MaxFreq
Conflict

2 The sum of inverter Maximum Speed (82) and inverter Overspeed Limit (83) exceeds inverter Maximum Freq

(55). Raise inverter Maximum Freq (55) or lower inverter Maximum Speed (82) and/or inverter Overspeed Limit
(83) so that the sum is less than or equal to inverter Maximum Freq (55).

Motor Type
Cflct

2 Inverter Motor Type (90) has been set to Sync Prm Mag or Sync Reluc, and one or more DC functions (for example,

DC Boost, DC Brake, etc.) have been activated. DC injection functions are incompatible with synchronous motors
and may demagnetize them.

No Line Sync

1 Rectifier cannot synchronize to the AC line.

NP Hz Conflict

2 Fan/pump mode is selected in inverter Torq Perf Mode (53), and the ratio of inverter Motor NP Hertz (43) to

inverter Maximum Freq (55) is greater than 26.

Power Loss

1 Drive has sensed a power line loss.

Power Phased
ACB

1 Input power phases are connected ACB, two input phases must be switched.

Prechrg Actv

1 Drive is in the initial DC bus precharge state.

Speed Ref
Cflct

2 Inverter Speed Ref x Sel or inverter PI Reference Sel is set to Reserved.

Under-
Voltage

1 The bus voltage has dropped below a predetermined value.

VHz Neg Slope

2 Custom V/Hz mode has been selected in inverter Torq Perf Mode (53) and the V/Hz slope is negative.

Alarm

Ty

pe Description

Start

Stop–CF

Run

Run Fwd Run Rev Jog

Jog Fwd Jog Rev

Fwd/
Rev

Start
Stop–CF
Run
Run Fwd
Run Rev
Jog
Jog Fwd
Jog Rev
Fwd / Rev

Forward/Reverse

Run Reverse

Bus Regulation Mode B

Speed Select 1

Jog Forward

Acc2 / Dec2

Speed Select 2

Jog Reverse

Accel 2

Speed Select 3

Stop Mode B

Decel 2

Run Forward

Run