Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual
Page 163

Rockwell Automation Publication D2-3518-3 - May 2013
163
Chapter 9
The RMS input phase current I
s is displayed as x.x A.
The RMS input phase current I
t is displayed as x.x A.
The active input current is displayed as ±
x.x A. Motoring current is positive and
generating current is negative.
The reactive input current is displayed as
x.x A. This value should always be
near 0.
The RMS phase-to-phase input voltage V
rs is displayed as x.x V.
3
Input Current S
Range:
0.0...3276.7 A [0.1 A]
Default:
Read Only
Access:
0
Path: Monitor > Metering
See also:
4
Input Current T
Range:
0.0...3276.7 A [0.1 A]
Default:
Read Only
Access:
0
Path: Monitor > Metering
See also:
5
Active Current
Range:
±
3276.7 A [0.1 A]
Default:
Read Only
Access:
0
Path: Monitor > Metering
See also:
6
Reactive Current
Range:
0.0...3276.7 A [0.1 A]
Default:
Read Only
Access:
0
Path: Monitor > Metering
See also:
7
Input Voltage RS
Range:
0.0...3276.7 V AC [0.1V AC]
Default:
Read Only
Access:
0
Path: Monitor > Metering
See also: