234

Rockwell Automation Publication D2-3518-3 - May 2013

Appendix A

Cooling System
Specifications (Refrigerant)

For coolant hardware connections, see

Figure 14 on page 37

through

Figure 17

on page 40

.

Motor Overload Protection

LF200460AAR

LF200608CCR

LF200900CCR

LF201215CCR

Max. Input Current (Amps)

405

608

900

1215

Max. Output Current (Amps)

405

608

900

1215

Coolant Temp Range

(1)

5...40 °C (41...104 °F)

5...40 °C (41...104 °F)

5...40 °C (41...104 °F)

5...40 °C (41...104 °F)

Minimum Coolant Flow Rate (GPM)

7

7

15

15

Pressure Drop (psig) from Power Module Inlet to Outlet @
Min. Coolant Flow Rate

10

10

10

10

Coolant

WEG25

(2)

WEG25

(2)

WEG25

(2)

WEG25

(2)

Max. Inlet Pressure (PSI)

180

180

180

180

Max. Heat Load

6000 Watts

9000 Watts

12,000 Watts

18,000 Watts

(1) Coolant temperature must be above the dew point to prevent condensation. If the water temperature is below the dew point, the appropriate water flow rate control is needed. Consult Rockwell

Automation.

(2) WEG25 = good quality or distilled water/ethylene glycol 25% by volume. An approved inhibited, silicate-free ethylene glycol is Ucartherm, a product of Dow Chemical Company.

ATTENTION: Ethylene glycol solutions must be inhibited and silicate-free. Use
of uninhibited and silicate-containing solutions can damage the cooling
system.

Condition

Specification

Electronic Motor Overload Protection:

Provides class 10 motor overload protection according to NEC article 430.
Does not provide speed sensitive overload protection, thermal memory
retention and motor over-temperature sensing according to NEC article
430.126 (A) (2). If such protection is needed in the end-use product, it
must be provided by additional means.