Chapter 9
Sets the boost level for steady state or deceleration when Fan/Pmp V/Hz or
Custom V/Hz modes are selected in Torque Perf Mode (53).
Sets the voltage the drive will output at Break Frequency (72).
Sets the frequency the drive will output at Break Voltage (71).
Sets the method of speed regulation.
70
Run Boost
Range:
0.0 to Motor NP Volts x 0.25 [0.1V AC]
Default:
Based on drive rating
Access:
1
Path: Motor Control > Volts per Hertz
See also:
53, 69, 83
71
Break Voltage
Range:
0.0 to Motor NP Volts [0.1V AC]
Default:
Motor NP Volts x 0.25
Access:
1
Path: Motor Control > Volts per Hertz
See also:
53, 72, 83
72
Break Frequency
Range:
0.0...250.0 [0.1 Hz]
Default:
Motor NP Freq x 0.25
Access:
1
Path: Motor Control > Volts per Hertz
See also:
53, 71, 83
80
Speed Mode
Range:
0 = Open Loop
1 = Slip Comp
2 = Process PI
Default:
0 = Open Loop
Access:
1
Path: Speed Command > Spd Mode & Limits
See also:
124...138