Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual

Page 87

Advertising
background image

Rockwell Automation Publication D2-3518-3 - May 2013

87

Chapter 9

Sets the boost level for steady state or deceleration when Fan/Pmp V/Hz or
Custom V/Hz modes are selected in Torque Perf Mode (53).

Sets the voltage the drive will output at Break Frequency (72).

Sets the frequency the drive will output at Break Voltage (71).

Sets the method of speed regulation.

70

Run Boost

Range:

0.0 to Motor NP Volts x 0.25 [0.1V AC]

Default:

Based on drive rating

Access:

1

Path: Motor Control > Volts per Hertz

See also:

53, 69, 83

71

Break Voltage

Range:

0.0 to Motor NP Volts [0.1V AC]

Default:

Motor NP Volts x 0.25

Access:

1

Path: Motor Control > Volts per Hertz

See also:

53, 72, 83

72

Break Frequency

Range:

0.0...250.0 [0.1 Hz]

Default:

Motor NP Freq x 0.25

Access:

1

Path: Motor Control > Volts per Hertz

See also:

53, 71, 83

80

Speed Mode

Range:

0 = Open Loop
1 = Slip Comp
2 = Process PI

Default:

0 = Open Loop

Access:

1

Path: Speed Command > Spd Mode & Limits

See also:

124...138