156

Rockwell Automation Publication D2-3518-3 - May 2013

Chapter 9

mode to use. If this input function is not configured, then Bus Reg Mode A
selects which bus regulation mode to use.

15...17 = Speed Select 1, 2, 3:

One, two, or three digital input functions can be

used to select the speed reference used by the drive, and they are called the Speed
Select input functions. The current open/closed state of all Speed Select input
functions combine to select which source is the current speed reference.

There are seven possible combinations of open/closed states for the three input
functions, and thus seven possible parameters can be selected. The seven
parameters are: Speed Ref A Sel and Preset Speed 2 through Preset Speed 7.

If the Speed Select input functions select Speed Ref A Sel, then the value of that
parameter further selects a reference source. There are a large number of possible
selections, including all six presets.

If the input functions directly select one of the preset speed parameters, then the
parameter contains a frequency that is to be used as the reference.

The Speed Select input function configuration process involves assigning the
functionality of the three possible Speed Select input functions to physical digital
inputs. The three Speed Select inputs functions are called Speed Select 1, Speed
Select 2, and Speed Select 3, and they are assigned to physical inputs using the
Digital In“x”

Sel parameters.

Table 12

describes the various reference sources that can be selected using all

three of the Speed Select input functions. If any of the three Reference Select
input functions are not configured, the software still follows the table, but treats
the unconfigured inputs as if they are permanently open.

Table 12 - Effect of Speed Select Input State on Selected Reference

18 = Auto/Manual:

The Auto/Manual function allows a single control device to

assume exclusive control of reference select. The most recent peripheral (OIM or
terminal block) that makes a manual reference request is given control of the
reference.

If the Auto/Manual input function is closed, then the drive uses one of the analog
inputs (defined by TB Man Ref Sel) as the reference. If an OIM subsequently

Speed
Select 3

Speed
Select 2

Speed
Select 1

Parameter that determines reference:

Open

Open

Open

Speed Ref A Sel

Open

Open

Closed

Speed Ref B Sel

Open Closed

Open

Preset

Speed

2

Open

Closed

Closed

Preset Speed 3

Closed

Open

Open

Preset Speed 4

Closed

Open

Closed

Preset Speed 5

Closed

Closed

Open

Preset Speed 6

Closed

Closed

Closed

Preset Speed 7