Chapter 9

Sets the response time of slip compensation.

Parameters in the Slip Comp Group (121...123) are used to enable and tune the
slip compensation regulator. To allow the slip compensation regulator to control
drive operation, Speed Mode (80) must be set to 1 (Slip Comp).

Displays the present amount of adjustment being applied as slip compensation.

Selects specific features of the PI regulator.

Figure 40 - PI Configuration (124)

Bit 0 – Excl Mode (Exclusive Mode)

Enabled = Selects speed regulation.

Disabled = Selects trim regulation.

Bit 1 – Invert Error

Enables/disables the option to invert the sign of the PI error signal.
Enabling this feature creates a decrease in output for an increasing error
and an increase in output for a decreasing error.

122

Slip Comp Gain

Range:

1.0...100.0 [0.1]

Default:

40.0

Access:

1

Path: Speed Command > Slip Comp

See also:

80, 121, 122

123

Slip RPM Meter

Range:

-/+300.0 RPM

Default:

Read Only

Access:

1

Path: Speed Command > Slip Comp

See also:

80, 121, 122

124

PI Configuration

Range:

See

Figure 40

Default:

See

Figure 40

Access:

1

Path: Speed Command > Process PI

See also:

125...138

0

0

0

0

0

0

0

0

x

x

x

x

x

x

x

x

0

0

1

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Enabled
0 =Disabled
x =Reserved