Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual

Page 168

Advertising
background image

168

Rockwell Automation Publication D2-3518-3 - May 2013

Chapter 9

The rectifier rated RMS input voltage is displayed as

x.x V AC.

The rectifier rated RMS input current is displayed as

x.x A.

The rectifier software version number is displayed as

x.xxx.

The allowed level of imbalance in input voltage entered as

x.x%.

An Input V Imbalance fault (fault 226) is generated if Line V Imbalance (23) is
greater than V Imbalance Lmt (60) for this amount of time.

27

Rated Volts

Range

0.0...6553.5 V AC [0.1V AC]

Default:

Read Only

Access:

0

Path: Monitor > Drive Data

See also:

28

Rated Amps

Range:

0.0...6553.5 A [0.1 A]

Default:

Read Only

Access:

0

Path: Monitor > Drive Data

See also:

29

Control SW Ver

Range:

x.xxx

Default:

Read Only

Access:

0

Path: Monitor > Drive Data

See also:

60

V Imbalance Lmt

Range:

Path: 0.0 to 20.0% [0.1%]

Default:

10.0

Access:

0

Path: Configuration > AC Line

See also:

23, 61

61

V Imbalance Time

Range:

1.0...10.0 seconds [0.1 seconds]

Default:

1.0

Access:

0

Path: Configuration > AC Line

See also:

23, 60

Advertising