Determining drive status using the status leds – Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual

Page 196

Advertising
background image

196

Rockwell Automation Publication D2-3518-3 - May 2013

Chapter 10

5.

Measure the DC bus potential with a voltmeter while standing on a
non-conductive surface and wearing insulated gloves. See

Figure 77

for

Frame 3, and

Figure 78

for Frame 4.

6.

Once the drive has been serviced, reattach the power module cover and
close the enclosure door.

7.

Turn on the circuit breaker.

Figure 77 - Location of DC Bus Measuring Points (Frame 3)

Figure 78 - Location of DC Bus Measuring Points (Frame 4)

Determining Drive Status
Using the Status LEDs

The inverter and rectifier sections each have a status LED.

For Frame 3 drives, the status LEDs are located on the Communication Interface
board, and are labeled on the board itself as INV STATUS (inverter) and
ACTIVE RECT. STATUS

(rectifier). See

Figure 79

.

For Frame 4 drives, the status LEDs are located on the Control Board, and are
labeled on the board itself as B2 (inverter) and B1 (rectifier). See

Figure 80

.

DC Bus measurement points on
laminated bus assembly.
0.25 in. x .032 in. male faston.
Accessible by removal of top cover.

Front View of Frame 3 Power Module

Right Side View of
Frame 3 Power Module

DC

POS.

(+)

DC

NEG.

(-)

Front View of Frame 4 Power Module

Right Side View of
Frame 4 Power Module

DC Bus measurement points on laminated bus assembly.
0.25 in. x .032 in. male faston.
Accessible by removal of top cover.