76

Rockwell Automation Publication D2-3518-3 - May 2013

Chapter 9

The usable range and default for this parameter depends on the operational mode
of the analog output, which in turn depends both on the capabilities of the analog
output hardware and the current value of parameter Analog Out Config (340).

Table 6

describes the details for usable range and default.

Table 6 - Appl Analog Output (31) usable range and default

The value in the Default column of

Table 6

is in effect when the drive powers up.

This parameter value is not stored in non-volatile memory.

For frame 3 drives (firmware version 1.x), the user-configurable analog output
hardware is located on the optional Standard I/O Board. This parameter is not
usable if the optional Standard I/O Board is not present. See

Standard I/O Board

Description (Frame 3 Only) on page 27

for terminal block assignments.

For frame 4 drives (firmware version 2.x), the user-configurable analog output
hardware is located on the Combined I/O Board. See

Combined I/O Board

Description (Frame 4 Only) on page 29

for terminal block assignments.

Selects how rectifier sequencing operates.

Mode

Usable Range

Default

0...10V (unipolar)

0.000...10.000V

0.000V

-10...10V (bipolar)

-10.000...10.000V

0.000V

4...20 mA

0.000...20.000 mA

0.000 mA

32

Rctfr Config

Range:

0 = Run at Start
1 = Run at Power Up
2 = Manual Control
3 = Diode Rectifier

Default:

0

Access:

1

Path: Monitor > Application

See also:

30

0

= The precharge is closed and voltage regulation is enabled when the

inverter is requested to start.

1

= The precharge is closed and voltage regulation is enabled when power is

turned on.

2

= The closing of the precharge and enabling of voltage regulation is

controlled by some other device writing into inverter Appl Digital Out
(30).

3

= Rectifier consists of a diode bridge. This mode is for engineering use only.