Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual

Page 184

Advertising
background image

184

Rockwell Automation Publication D2-3518-3 - May 2013

Chapter 9

Frame 4 drives (firmware version 2.x) only:

Figure 73 - Dig In Status (216) Frame 4

On the Frame 4 drive, precharge contactor feedback appears in bit 15 of this
parameter.

A 1 in bit 15 indicates that all of the precharge contactors are closed.

A 0 in bit 15 indicates that at least one of the contactors is open.

On the Frame 4 drive, Combined I/O board Digital Inputs 1 and 2 are used to
select measurements to be displayed on the optional input voltage and current
meters, as described in

Table 14

.

Table 14 - AC Line I/O Digital Inputs 3 and 4 (Frame 4)

Displays commanded status of the digital outputs that are controlled by the
rectifier.

See

AC Line I/O Board Description (Frame 3 Only) on page 25

through

Combined I/O Board Description (Frame 4 Only) on page 29

for a description

of I/O hardware that is present on this drive and is controlled by the rectifier.

Dig. In 2

Dig. In 1

Selected Measurement

0 0 Iv,

Vst

0 1 Iw,

Vtr

1 0 Iu,

Vrs

1 1 Iu,

Vrs

217

Dig Out Status

Range:

Bits on/off

Default:

Read Only

Access:

0

Path: Utility > Status

See also:

inverter 30

0

0

x x x x x

x

x x x

x

x

x

x

0

0

1

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Input Active
0

0

=Input Not Active

x =Reserved

Bit #

Combined I/O Dig. Input 1

Combined I/O Dig. Input 2

Precharge Feedback

Nibble 1

Nibble 2

Nibble 3

Nibble 4