Rockwell Automation Publication D2-3518-3 - May 2013

Chapter 9

Sets the rate of deceleration for all speed decreases.

(Max Speed ÷ Decel Time) = Decel Rate

Two decel times exist to enable deceleration rate changes on the fly using a
building automation system command or digital input, if configured.

Sets the percentage of acceleration or deceleration time that is applied to the
ramp as S Curve. Time is added; 1/2 at the beginning and 1/2 at the end of the
ramp.

Selects the source for the adjustment of current limit (i.e., parameter, analog
input, etc.).

Defines the RMS current limit value when Current Lmt Sel (147) = Cur Lim
Val.

142
143

Decel Time 1
Decel Time 2

Range:

0.1...100.0 sec [0.1 sec]

Default:

10.0 sec

Access:

142 = 0
143 = 0

Path: Dynamic Control > Ramp Rates

See also:

142, 143, 146, 361...366

146

S Curve %

Range:

0...100% [1%]

Default:

0%

Access:

0

Path: Dynamic Control > Ramp Rates

See also:

140...143

147

Current Lmt Sel

Range:

0 = Curr Lim Val
1 = Analog In 1
2 = Analog In 2

Default:

0 = Cur Lim Val

Access:

0

Path: Dynamic Control > Load Limits

See also:

148, 149

148

Current Lmt Val

Range:

Based on Drive Type [0.1 A]

Default:

Based on Drive Type (approximately 150%)

Access:

0

Path: Dynamic Control > Load Limits

See also:

147, 149