For the LiquiFlo 2.0 drive, always set this parameter to 0 (Disabled).

Selects whether the internal or an external DB resistor is used.

Proportional gain for the bus regulator. Used to adjust regulator response.

ATTENTION: The adjust freq portion of the bus regulator function is extremely
useful for preventing nuisance overvoltage faults resulting from aggressive
decelerations, overhauling loads, and eccentric loads. It forces the output
frequency to be greater than commanded frequency while the drive’s bus
voltage is increasing towards levels that would otherwise cause a fault.
However, it can also cause either of the following two conditions to occur:

Fast positive changes in input voltage (more than a 10% increase within

6 minutes) can cause uncommanded positive speed changes; however, an
OverSpeed Limit fault occurs if the speed reaches Max Speed + Overspeed
Limit. If this condition is unacceptable, action should be taken to 1) limit supply
voltages within the specification of the drive, and 2) limit fast positive input
voltage changes to less than 10%. Without taking such actions, if this
operation is unacceptable, the adjust freq portion of the bus regulator function
must be disabled (see parameters 161 and 162).

Actual deceleration times can be longer than commanded deceleration times;

however, a Decel Inhibit fault is generated if the drive stops decelerating
altogether. If this condition is unacceptable, the adjust freq portion of the bus
regulator must be disabled (see parameters 161 and 162). In addition,
installing a properly sized dynamic brake resistor provides equal or better
performance in most cases.

Note that these faults are not instantaneous and have shown test results that take
between 2 and 12 seconds to occur.

163

DB Resistor Type

Range:

0 = Internal Res
1 = External Res
2 = None

Default:

2 = None

Access:

0

Path: Dynamic Control > Stop/Brake Modes

See also:

161, 162

164

Bus Reg Kp

Range:

0...10000

Default:

1200

Access:

1

Path: Dynamic Control > Stop/Brake Modes

See also: