277 start mask, 278 jog mask, 279 direction mask – Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual

Page 134: 280 reference mask

Advertising
background image

134

Rockwell Automation Publication D2-3518-3 - May 2013

Chapter 9

Controls which modules can issue start commands.

Controls which modules can issue jog commands.

Figure 61 - Jog Mask (278)

Controls which modules can issue forward/reverse direction commands.

Controls which modules can select an alternate reference. Speed Ref A, B Sel or
Preset 1 - 7 (90, 93, 101...107).

277

Start Mask

Range:

See Logic Mask (276)

Default:

See Logic Mask (276)

Access:

1

Path: Communication > Masks & Owners

See also:

288...297

278

Jog Mask

Range:

See

Figure 61

Default:

See

Figure 61

Access:

1

Path: Communication > Masks & Owners

See also:

288...297

279

Direction Mask

Range:

See Jog Mask (278)

Default:

See Jog Mask (278)

Access:

1

Path: Communication > Masks & Owners

See also:

288...297

280

Reference Mask

Range:

See

Figure 62

Default:

See

Figure 62

Access:

1

Path: Communication > Masks & Owners

See also:

288...297

0 0

0 0

0

0

x

x

x

x

x

x

x

x

x

x

0

0

1

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Control Enabled
0 =Control Disabled
x =Reserved

Bit #

Digital In

DPI P

or

t 1

DPI P

or

t 2

DPI P

or

t 3

DPI P

or

t 4

DPI P

or

t 5

Nibble 1

Nibble 2

Nibble 3

Nibble 4

Factory Default Bit Values