Figure 62 - Reference Mask (280)

Controls which modules can select Accel Time 1, 2 (140, 141).

Controls which modules can select Decel Time 1, 2. (142, 143)

Controls which modules can clear a fault.

Controls which modules can issue MOP commands to the drive.

281

Accel Mask

Range:

See Reference Mask (280)

Default:

See Reference Mask (280)

Access:

1

Path: Communication > Masks & Owners

See also:

288...297

282

Decel Mask

Range:

See Reference Mask (280)

Default:

See Reference Mask (280)

Access:

1

Path: Communication > Masks & Owners

See also:

288...297

283

Fault Clr Mask

Range:

See Reference Mask (280)

Default:

See Reference Mask (280)

Access:

1

Path: Communication > Masks & Owners

See also:

288...297

284

MOP Mask

Range:

See Reference Mask (280)

Default:

See Reference Mask (280)

Access:

1

Path: Communication > Masks & Owners

See also:

288...297

285

Local Mask

Range:

See Reference Mask (280)

Default:

See Reference Mask (280)

Access:

1

Path: Communication > Masks & Owners

See also:

288...297

1 1

1 1

1

1

x

x

x

x

x

x

x

x

x

x

0

0

1

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Control Enabled
0 =Control Disabled
x =Reserved

Bit #

Digital In

DPI P

or

t 1

DPI P

or

t 2

DPI P

or

t 3

DPI P

or

t 4

DPI P

or

t 5

Nibble 1

Nibble 2

Nibble 3

Nibble 4

Factory Default Bit Values