Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual

Page 172

Advertising
background image

172

Rockwell Automation Publication D2-3518-3 - May 2013

Chapter 9

Frame 4 drives (firmware version 2.x) only:

Figure 71 - Rectifier Status (101) Frame 4

Selects whether DC bus voltage (Vdc) optimization is enabled or disabled.

At low speeds the inverter requires a lower DC bus voltage, so the voltage
supplied by the rectifier can be lowered to reduce switching losses. The DC bus
voltage must be greater than the peak of the AC line, so this feature is more useful
with 400V AC input.

If Vdc Optimize (102) is set to Disabled, the DC bus voltage generated by the
rectifier

while the rectifier or the entire drive is running is calculated based on a

combination of the value of Vdc Reference (103) and measured line-to-line
voltage of the AC line. In this case, Vdc Reference (103) defines the minimum
DC bus voltage that the rectifier commands while it is running.

If Vdc Optimize (102) is set to Enabled, the DC bus voltage generated by the
rectifier

while the rectifier or the entire drive is running is calculated based on a

combination of the DC bus level necessary to provide the motor voltage required
by the inverter and the measured line-to-line voltage of the AC line. Vdc
Reference (103) is not used in this case.

If Vdc Optimize (102) is set to Enabled, the DC bus voltage required by the
inverter

is calculated from the output frequency of the inverter and the value of

the Max Motor Volts (107), Max Motor Freq (108), and Base Motor Freq (109)
rectifier parameters.

102

Vdc Optimize

Range:

0 = Disabled
1 = Enabled

Default:

0 = Disabled

Access:

0

Dynamic Control > Bus Voltage

See also:

103, 104, 107, 108, 109

x

0

0

1

1

2

3

4

5

6

7

8

9

11

12

13

14

15

x =Reserved

Bit #

OK to Run I

nverter

Rectifier Running

Rectifier F

aulted

Rectifier in Limit

Rectifier Synch

roniz

ed

Rectifier Phased ACB

Rectifier at

V

oltage

Rectifier Regener

ating

Fault Reset Echo

Nibble 1

Nibble 2

Nibble 3

Nibble 4

Rectifier Carrier Sync

Loop Control Enable

Appl. Digital Out 3

Bit 0 indicates OK to

run

Appl. Digital Out 4

Standb

y

Advertising