170

Rockwell Automation Publication D2-3518-3 - May 2013

Chapter 9

Defines the allowed power dip time that will not cause a Ride Thru Abort fault
(fault 221).

Setting a value of 0 generates a fault on a loss of a single line cycle.

Setting a value of 0.10 allows line synchronization to be lost for 100 msec
before a fault is generated.

A fault is also generated if the bus voltage drops below the power loss threshold
before the ride-through time has elapsed.

The commanded state of the rectifier.

Frame 3 drives (firmware version 1.x) only:

Figure 68 - Rectifier Control (100) Frame 3

65

Ride Through Sec

Range:

0.00...60.00 seconds [x.xx seconds]

Default:

1.00

Access:

0

Path: Configuration > AC Line

See also:

64, inverter 184, 185

100

Rectifier Contrl

Range:

See

Figure 68

and

Figure 69

Default:

N/A

Access:

0

Path: Dynamic Control > Control and Status

See also:

inverter 33

IMPORTANT

This parameter is used for communication between the inverter and the
rectifier. Do not write to this parameter using VS Utilities, DriveExplorer, or an
OIM. Its value changes according to the operational state of the drive.

x

x

x

0

0

1

1

2

3

4

5

6

7

8

9

11

12

13

14

15

x =Reserved

Bit #

AC

Line I/O:

Dig.

Output 1

AC

Line I/O:

Dig.

Output

2

AC

Line

I/O:

Dig.

Output 3

AC

Line I/O:

Dig.

Output 4

AC

Line I/O:

Dig.

Output 5

AC

Line I/O

: Dig.

Output 6

Close Pre-charge

Enab

le Rectifie

r

Reset Recifier Fau

lt

Inverter Fault

Network Loss

DC Bus Limit

Extend

Nibble 1

Nibble 2

Nibble 3

Nibble 4