Rockwell Automation Liqui-Flo V2.0 AC Drive User Manual

Page 79

Advertising
background image

Rockwell Automation Publication D2-3518-3 - May 2013

79

Chapter 9

Displays a fault from the rectifier. The rectifier writes a fault code into this
parameter through a data link.

Set to match the type of motor connected: Induction, Synchronous Reluctance,
or Synchronous Permanent Magnet.

Set to the motor nameplate rated volts. The motor nameplate base voltage
defines the output voltage when operating at rated current, rated speed, and rated
temperature.

Set to the motor nameplate rated full load amps. The motor nameplate FLA
defines the output amps when operating at rated voltage, rated speed, and rated
temperature. It is used in the motor thermal overload and in the calculation of
slip.

35

Rctfr Fault

Range:

0...299

Default:

Read Only

Access:

1

Path: Monitor > Application

See also:

40

Motor Type

Range:

0 = Induction
1 = Synchr Reluc
2 = Synchr PM

Default:

0 = Induction

Access:

1

Path: Motor Control > Motor Data

See also:

41

Motor NP Volts

Range:

0.0 to Drive Rated Volts [0.1V AC]

Default:

Based on Drive Type

Access:

0

Path: Motor Control > Motor Data

See also:

42

Motor NP FLA

Range:

0.0 to Rated Amps x 2 [0.1 A]

Default:

Based on Drive Type

Access:

0

Path: Motor Control > Motor Data

See also:

47, 48