Rockwell Automation Publication D2-3518-3 - May 2013

95

Chapter 9

Figure 39 - Trim Out Select (118)

Scales the upper value of the Trim In Select (117) selection when the source is an
analog input.

Scales the lower value of the Trim In Select (117) selection when the source is an
analog input.

Sets the amount of compensation to drive output at motor FLA. If parameter 61
(Autotune) = 3 (Calculate), changes made to this parameter are not accepted.

Parameters in the Slip Comp Group (121...123) are used to enable and tune the
slip compensation regulator. To allow the slip compensation regulator to control
drive operation, Speed Mode (80) must be set to 1 (Slip Comp).

119

Trim Hi

Range:

-/+Maximum Speed [0.1 Hz]

Default:

60.0 Hz

Access:

1

Path: Speed Command > Speed Trim

See also:

82, 117

120

Trim Lo

Range:

-/+Maximum Speed [0.1 Hz]

Default:

0.0 Hz

Access:

1

Path: Speed Command > Speed Trim

See also:

117

121

Slip RPM @ FLA

Range:

0.0...1200.0 RPM

Default:

Based on Motor NP RPM

Access:

1

Path: Speed Command > Slip Comp

See also:

61, 80, 122, 123