To restore all parameters to their factory-default values, select Reset Defaults
from the Memory Storage menu.

Note that the parameter values are retained through a line dip or power
shutdown.

Loading and Saving User Sets

Drive configurations, called user sets, can be saved and recalled for use at any
time. Up to three user sets can be saved in the LiquiFlo drive.

To save the current drive configuration, select Save to User Set from the
Memory Storage menu.

To recall, or load, a user set, select Load Frm Usr Set from the Memory
Storage menu.

To identify which user set is active, select Active User Set from the Memory
Storage menu. The name of the last user set to be loaded into the drive is
displayed. Active Set means factory defaults have been restored.

Monitoring the Drive Using
the Process Display Screen on
the OIM

The process display screen

enables you to monitor up to three process variables.

You can select the display, parameter, scale, and text for each process variable
being displayed.

The

key toggles between the programming screen and the process display

screen. From the Main Menu screen, press F1 or F2 to select the process display
screen. In addition, the process display screen becomes active if no keys have been
pressed before the display timeout period expires. See

Setting the Display

Timeout Period on page 246

for information about setting the display timeout

period.

Figure 97 - Process (User) Display Screen

ESC/

PROG

P0: LiquiFlo 2.0

Auto

Stopped

Fltq

0.00

V olts
A m ps
H z

0.00
0.00

Customize up to
eight F-Key labels

Select up to
three process
variables to
monitor, and
customize the
text displayed

Scale the output
values to suit the
application

Advertising