Chapter 9

Sets the lowest input value to the user-configurable analog input 1 scaling block.
See Analog In 1 Hi (322) for more information and a scaling example.

Analog In 1 Hi sets the highest input value to the user-configurable analog input
1 scaling block. See

AC Line I/O Board Description (Frame 3 Only) on page 25

through

Combined I/O Board Description (Frame 4 Only) on page 29

for a

description of I/O hardware that is present on this drive and is controlled by the
inverter.

Selects drive response when an analog signal loss is detected on user-configurable
analog input 1:

1.0V = signal loss

1.5V = end of signal loss

2.0 mA = signal loss

3.0 mA = end of signal loss

See

AC Line I/O Board Description (Frame 3 Only) on page 25

through

Combined I/O Board Description (Frame 4 Only) on page 29

for a description

of I/O hardware that is present on this drive and is controlled by the inverter.

323

Analog In 1 Lo

Range:

4.000...20.000 mA [0.001 mA]
-/+10.000V [0.1V]
0.0...10.000V [0.1V]

Default:

4 mA

Access:

0

Path: Inputs & Outputs > Analog Inputs

See also:

91, 92, 320

324

Analog In 1 Loss

Range:

0 = Disabled
1 = Fault
2 = Hold Input (use last frequency command)
3 = Set Input Lo (use Minimum Speed as frequency command)
4 = Set Input Hi (use Maximum Speed as frequency command)
5 = Goto Preset1 (use Preset 1 as frequency command)
6 = Hold OutFreq (maintain last output frequency)

Default:

0 = Disabled

Access:

1

Path: Inputs & Outputs > Analog Inputs

See also:

91, 92, 320