Chapter 9

Frame 3 drives (firmware version 1.x) only:

Figure 72 - Dig In Status (216) Frame 3

On the Frame 3 drive, AC Line I/O Digital Input 1 is used for precharge
contactor feedback.

A 1 in bit 0 indicates that all of the precharge contactors are closed.

A 0 in bit 0 indicates that at least one of the contactors is open.

Also on the Frame 3 drive, bit 9 indicates that AC line rotation has been
determined, bit 8 indicates whether the rotation is ACB (not usable) or ABC
(usable), and bits 10...15 provide information about the internal state of the AC
line synchronization function of the AC Line I/O board. Bits 10...15 are for
engineering use only.

On the Frame 3 drive, AC Line I/O Digital Inputs 3 and 4 are used to select
measurements to be displayed on the optional input voltage and current meters,
as described in

Table 13

.

Table 13 - AC Line I/O Digital Inputs 3 and 4 (Frame 3)

Dig. In 4

Dig. In 3

Selected Measurement

0 0

Iv,

Vst

0 1

Iw,

Vtr

1 0

Iu,

Vrs

1 1

Iu,

Vrs

0

0

0

0

x

x

x

x

x

x

0

0

1

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Input Active
0

0

0

0

0

0

0

=Input Not Active

x =Reserved

Bit #

AC Line I/O Dig. Input 1

AC Line I/O Dig. Input 2

AC Line I/O Dig. Input 3

AC Line I/O Dig. Input 4

ACB Rotation

Rotation Valid

Vab Ready

Vbc Ready

Vca Ready

Vca Edge

Nibble 1

Nibble 2

Nibble 3

Nibble 4